AC2035

AC2035

Produktcode: EEMS/Module/4DI/4DO/T/CCT
Marke: IFM
  • Easy to mount and wire
  • For the connection of sensors and actuators with cable entry
  • Connection via cage clamps
  • Clearly visible powerful LEDs for displaying operation, switching status and error
Application field installation
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 230
Max. current load total [A] 4
Integrated watchdog yes
Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 4
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply [V] 20...30
Max. total current rating of inputs [mA] 200
Input current High [mA] > 5
Input current low [mA] < 3
Switching level high [V] > 10
Digital inputs protected against short circuits yes
Number of digital outputs 4
Circuit PNP
Voltage range DC [V] 24; (to PELV)
Max. current load per output [mA] 1000; (DC-12 / DC-13)
Short-circuit proof yes
Electrically separated yes
Actuator supply outputs AUX
Ambient temperature [°C] -25...60
Protection IP 65
EMC
EN 50295
AS-i profile S-7.F.F
AS-i I/O configuration [hex] 7
AS-i ID code [hex] F.F
Data bits
Data bit D0 D1 D2 D3
bidirectional I-1 / O-1 I-2 / O-2 I-3 / O-3 I-4 / O-4
Parameter bits
Parameter bit Function
P0 watchdog for all outputs : activated * / disabled
P1 not used
P2 not used
P3 not used
Weight [g] 317
Type of mounting AS-i interface to FC-E or SC lower parts
Material PA 6-GF30; stainless steel (1.4305 / 303)
Display
Power LED, green
Function LED, yellow
Module connection Flat cable
Remarks
Inputs and outputs must be electrically isolated.
Pack quantity 1 pcs.
cage clamps:

AC2035 Dokümanları

Dateinamen Download-Link
AC2035.pdf Herunterladen

Ein Angebot bekommen