AC514A

AC514A

Produktcode: ClassicL 2DO-Y 2DI-Y II 3D
Marke: IFM
  • Easy toolless installation
  • Three selectable directions of the flat cable mounting
  • Clearly visible powerful LEDs for displaying operation, status and function
  • For applications in hazardous areas
  • Robust M12 connectors for connecting sensors and actuators
Application AS-i ATEX module
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 150
Max. current load total [A] 2
Integrated watchdog yes
Number of inputs and outputs Number of digital inputs: 2; Number of digital outputs: 2
Number of digital inputs 2
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply [V] 18...30; (via flat cable)
Max. total current rating of inputs [mA] 100
Input current High [mA] 6...10
Input current low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Number of digital outputs 2
Circuit PNP
Voltage range DC [V] 15...30; (to PELV; via flat cable)
Max. current load per output [mA] 1000; (utilization category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1))
Short-circuit proof yes
Electrically separated yes
Ambient temperature [°C] -10...50
Protection IP 50
ATEX marking II 3D Ex tc IIIB T80°C Dc X IP50
EMC
EN 50295
IEC 61000-6-2
MTTF [years] 192
AS-i version 2.11; 3.0
AS-i addressing Addressing socket
Extended addressing mode yes
AS-i profile S-B.A.E
AS-i I/O configuration [hex] B
AS-i ID code [hex] A.E
AS-i certificate pending yes
Data bits
Data bit D0 D1 D2 D3
Input - - 3 4
Socket - - I-3/4 I-3/4 I-4
Pin - - 4 2 4
Output 1 2 - -
Socket O-1/2 O-1/2 / O-2 - -
Pin 4 2 4 - -
Weight [g] 239.5
Type of mounting AS-i flat cable connection
Material PA; Piercing contacts: CuSn6 nickel-plated and tin-plated
Display
Power LED, green
errors LED, red
Function LED, yellow
Module connection Flat cable
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
impact protection housing:, E7000A
Remarks
Mechanical protection has to be implemented.
Otherwise the unit must be installed together with the impact protection housing (E7000A).
Do not connect any of the following points to an external potential:
I-, I+, I-3/4, I-4
The connections are electrically connected with the AS-i cable.
Inputs and outputs must be electrically isolated.
Pack quantity 1 pcs.
Connection quick mounting technology for AS-i flat cable: ; three selectable directions
Connection Connector: M12
Connection Connector: M12

AC514A Dokümanları

Dateinamen Download-Link
AC514A.pdf Herunterladen

Ein Angebot bekommen