AC528A

AC528A

Produktcode: AirBox 2x3/2 4DI-Y II 3D
Marke: IFM
  • For the decentralized triggering of cylinders and valve actuators
  • Combination of AS-i I/O module and solenoid valve
  • High energy efficiency due to decentralized application near the actuator
  • Reduced installation and wiring complexity
  • Easy toolless installation
Application AS-i ATEX module
Operating voltage [V] 26.5...31.6 DC
Max. current consumption from AS-i [mA] 280
Integrated watchdog yes
Number of inputs and outputs Number of digital inputs: 4; Number of pneumatic outputs: 2
Number of digital inputs 4
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Voltage supply [V] 20...30; (via flat cable)
Max. total current rating of inputs [mA] 200
Input current High [mA] 6...10
Input current low [mA] 0...2
Switching level high [V] > 11
Digital inputs protected against short circuits yes
Electrical design AS-i
Number of pneumatic outputs 2
Ambient temperature [°C] -10...50
Protection IP 50
ATEX marking II 3D Ex tc IIIB T80°C Dc X IP50
EMC
EN 50295
IEC 61000-6-2
MTTF [years] 287
AS-i version 2.11; 3.0
AS-i addressing Addressing socket
Extended addressing mode yes
AS-i profile S-7.A.E
AS-i I/O configuration [hex] 7
AS-i ID code [hex] A.E
AS-i certificate pending yes
Data bits
Data bit D0 D1 D2 D3
Input 1 2 3 4
Socket I-1/2 I-1/2 I-2 I-3/4 I-3/4 I-4
Pin 4 2 4 4 2 4
pneumatic output 2 4 - -
Weight [g] 415.5
Type of mounting quick mounting
Material PA; POM; Piercing contacts: CuSn6 nickel-plated and tin-plated
Pneumatic system 2 x 3/2-way slide valves (free from overlapping)
Operating pressure range [bar] 2...8
Operating pressure range [MPa] 0.2...0.8
Air flow at 6/5 bar [l/min] 500
Permissible compressed air non-lubricated compressed air class 6-3-1; lubricated compressed air class 6-3-4
Manual override pressing/releasing or pressing/turning/locking
Tube fittings 8 mm
Exhaust exhaust can be discharged through tube connection
Display
Power LED, green
errors LED, red
Function LED, yellow
Module connection Flat cable
Items supplied
lower part
Accessories (optional)
Mounting plate:, E74999
Module lower part:, E75000
Protective cap: M12, E73004
sealing plug:, E75231
impact protection housing:, E7000A
Silencer:, E75232
Push-in L-fitting:, E75228
Push-in T-fitting:, E75227
Remarks
Mechanical protection has to be implemented.
Otherwise the unit must be installed together with the impact protection housing (E7000A).
If not pneumatically operated, E75231 sealing plug must be inserted.
Avoid ingress of dirt and dust.
Do not connect any of the following points to an external potential:
L-, L+, I-1, I-2, I-3, I-4
The connections are electrically connected with the AS-i cable.
Please see the notes on compressed air and EMC/ESD under "Downloads"
Pack quantity 1 pcs.
Connection quick mounting technology for AS-i flat cable: ; three selectable directions
Connection Connector: M12
Pneumatic symbol
2 x 3/2-way slide valves (free from overlapping)